1-800-44-ENDOT(443-6368)
PIPE AND TUBING . DUCT AND INNERDUCT  

 

 

 

 

 

 

Premise Wiring
-Plenum
-Riser
-Zero Halogen Conduit
For the job you have, count on Endot's premise wiring products for cable management and protection. All of our raceways feature:
  • Super Flexible - will not kink in normal usage
  • Sizes ½", ¾", 1", 1 ¼", 1 ½", 2" - ALL with UL Listed pull line.
  • Halogen Free for applications requiring Zero Halogen raceway and innerduct.
  • Flexible - will not kink in normal usage
  • Never Brittle even in cold weather … unlike PVC products
  • Sequential footmarks.
  • A variety of packaging options, from 250' coils to 96" reels.

ENDOCOR/RI is UL Listed for Riser installations and conforms to NEC Article 770.53.  ENDOCOR/RI is designed for installation in risers shafts in buildings.

ENDOCOR/RI is a corrugated, non-metallic raceway that is very flexible for ease of installation, yet strong enough to protect delicate fiber optic cables.  Use of ENDOCOR raceways for premise wiring provides a clean low friction installation path for fiber optic cables and allows for future replacement of cable if upgrades are necessary.

ENDOCOR/RI is available in sizes from ˝” ID through 2” ID and all sizes can be supplied with UL Listed pull line.

ENDOCOR/RI raceway is colored a natural white to provide quick identification and to eliminate confusion with outdoor innerduct that is usually colored orange.  ENDOCOR raceways are clearly printed with sequential footage marks.  Custom printing is available.

ENDOCOR/RI can be packaged in coils, boxed coils or put up on reels from 48” to 96” diameter.  Give us your packaging requirements and we will provide what you need.

ENDOCOR/RI can be provided with Riser cable pre-installed in the raceway.  Call us for details.

ENDOCOR RI is produced from nylon resin and is non-halogenated.  Nylon also is flexible at all temperatures and will not become brittle at low temperatures as other Riser products will.

The use of Riser Raceway does not eliminate the need for riser rated cable.


SPECIFICATIONS
NOMINAL
DIMENSIONS
-1/2"
- 3/4"
- 1"
- 1-1/4"
- 1-1/2"
- 2"
0.650" ID - 0.850" OD
0.870" ID - 1.125" OD
1.100" ID - 1.350" OD
1.250" ID - 1.600" OD
1.500" ID - 2.000" OD
2.000" ID - 2.500" OD
DESIGN - CORRUGATED - for flexibility
MATERIAL - AlliedSignal Capron® Resin
PACKAGING - HAND COILS of 250 ft. & 500 ft.
- REEL LENGTHS of 1,000 ft. or longer
PULL LINE or CABLE - Pre installed Kevlar pull tape or cable (up to 7/16") in diameter

ENDOCOR / RI

ACCEPTANCE CRITERIA

TEST METHOD

VALUE

UL STANDARD 2024
Maximum Flame Propagation UL 2024, sec.9 4.25 ft.
Maximum Damage Height UL 2024, sec.9 6.75 ft.
MECHANICAL PROPERTIES
Tensile Strength, Yield
Flexural Strength

ASTM D638
ASTM D790

7,800 PSI
9,200 PSI

THERMAL PROPERTIES
Melting Point

ASTM D789

420°F

Note: The use of Riser Raceway does not eliminate the need for Riser rated cable.
Additional downloads/print versions
Plenum Riser Cover Sheet
Riser List Price Sheet
PL & RI Specs
Riser Complete Part Number Chart
PL & RI & CE Part Number Chart
Plenum & Riser as FT-6 & FT-4